CX2-S0-03-810-32A-0614 [Carling Technologies]
Circuit Breaker; 断路器型号: | CX2-S0-03-810-32A-0614 |
厂家: | Carling Technologies |
描述: | Circuit Breaker |
文件: | 总10页 (文件大小:2747K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
CX-Series
Circuit Breaker
The CX-Series circuit breaker features a unique and
innovative arc-quenching configuration that allows the
breaker to safely handle high amperage and high DC
voltage applications in a compact package.
By using a patent pending magnetic flux boosting
terminal configuration, a strong magnetic field is created
thus motivating the arc into an enhanced arc chamber
improving the breaker’s overall performance and reliability.
The permanent magnets located at the entrance of the arc
chamber combined with the upper and lower arc runner
increase the magnetic blow out force and aid in motivating
the arc off of the contacts and into the arc chamber.
An enhanced arc chamber features arc splitter retainers
with integrated pressurizing walls, which facilitates heat
transfer from the arc thereby providing additional cooling
and quick transition into the magnetically induced splitter
plates. In turn, the twelve (12) splitter plates attract,
segment and cool the arc for full extinction.
Combined, these innovative features make the CX-Series
breaker the best in class, providing stable performance
even in the most demanding applications.
Additional Features:
UL 489B approved
Applications:
Temperature stable hydraulic/magnetic overcurrent sensing
The CX-Series is UL 489B approved and ideal for
technology.
integration into the combiner box or main disconnect of
photovoltaic renewable energy systems.
Optional relay trip circuit permitting remote operator system
shut down.
Ideally suitable for integration into Information
Choice of 6-32 or M3 mounting inserts providing secure panel
Technologies’ power distribution equipment utilizing
high DC voltage input.
mount installation.
Choice of handle colors and legends, consult factory for details.
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062-1177
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: sales@carlingtech.com • www.carlingtech.com
|
2
CX-Series Circuit Breaker - General Specifications
CX-Series Circuit Breaker
DESIGN FEATURES
MAGNETS
ARC SPLITTER RETAINER
w/ integrated pressurizing walls
UPPER ARC RUNNER
Aids in motivating arc off of movable
contact and into arc chamber
ꢀ12ꢁ ARC DEIONIZING
SPLITTER PLATES
HYDRAULIC/MAGNETIC
SENSING COIL
PATENT PENDING MAGNETIC FLUX
BOOSTING TERMINAL CONFIGURATION
Design enhances motivation
LOWER ARC RUNNER
Aids in motivating arc off of stationary
contact and into arc chamber
LARGE ARC GAP
To generate high arc voltages
of arc into arc chamber
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
CX-Series Circuit Breaker - General Specifications
3
Electrical Tables
Table A: Lists UL Listed (UL489) configuration and performance
Table B: Lists UL Recognized configurations and performance
capabilities as a Molded Case Circuit Breaker
capabilities as a Component Supplementary Protector
CX SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
CX SERIES TABLE B : UL1077 COMPONENT SUPPLEMENTARY PROTECTOR
VOLTAGE
VOLTAGE
CIRCUIT
CONFIGURATION
MAX CURRENT INTERRUPTING
NUMBER
MAX
CURRENT
RATING AMPS
INTERRUPTING
CAPACITY
(AMPS)
CIRCUIT
CONFIGURATION
NUMBER APPLICATION
RATING AMPS CAPACITY (AMPS) OF POLES
MAX. RATING FREQUENCY
OF POLES
CODE
MAX.
FREQUENCY
RATING
1
2
250
D.C.
D.C.
15
15
5,000
SERIES
300
300
440
440
600
600
D.C.
D.C.
D.C.
D.C.
D.C.
D.C.
1 - 75
76 - 125
1 -30
5,000
3,000
10,000
5,000
3,000
5,000
1
1
2
2
2
2
TC1, OL0, U3
TC1, OL0, U3
TC1, OL0, U3
TC1, OL0, U3
TC1, OL0, U3
TC1, OL0, U3
250 / 500
10,000
Table C: Lists UL Listed (UL489B) configuration and
performance capabilities as a Molded Case Switch
SERIES
31 - 50
1 - 75
76 - 100
CX SERIES TABLE C : UL489B LISTED PHOTOVATIC MOLDED CASE SWITCH
SWITCH ONLY1
600
D.C.
1 - 100
3,000
2 or 3
---
VOLTAGE
CIRCUIT
CONFIGURATION MAX RATING FREQUENCY POLES
CURRENT RATING INTERRUPTING
CONSTRUCTION
NOTES
Notes:
(AMPS)
RATING (AMPS)
1
Requries inclusion of a relay trip voltage coil
May have a third pole
that is a voltage
trip pole
600
600
DC
DC
21
42
50 - 100
600
SERIES
May have a fifth pole
that is a voltage
trip pole
110 - 175
600
Notes:
1
2
Two poles in series.
Two poles in series in parallel with 2 poles in series.
Electrical
Mechanical
Endurance
Max 10,000 ON-OFF operations @ 6
per minute; 6000 with rated current &
voltage, and 4,000 cycles mechanical.
Trips on overload even when actuator
is forcibly held in the “On” position.
The operating handle moves positively
to the “Off” position when an overload
causes the breaker to trip.
Maximum Voltage
Overload
600 VDC
50 operations at 600% of rated current
for UL489, and at 150% of rated
current for UL1077.
Trip Free
RESISTANCEPERPOLEVALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Current
(amps)
Tolerance
(%)
Trip Indication
1000
100
10
0.1 -5.0
5.1-20.0
20.1-125
15%
25%
35%
Environmental
O
H
M
S
Shock
Withstands 100 Gs, 6ms saw tooth
while carrying rated current per
1
MILPRF-55629 and MIL-STD-202G,
Method 213G, Test Condition “I”.
Instantaneous and ultra short curves
tested at 90% of rated current.
Withstands 0.060” excursion from 10-55
Hz & 10 Gs 55-500 Hz, at rated current
per MIL-PRF-55629 and MILSTD-
202G, Method 240D, Test Cond. A.
Instantaneous & ultrashort curves tested
at 90% of rated current.
MIL-PRF-55629 and MIL-STD-202G,
Method 106G, i.e., Ten 24-hour cycles at
+25°C to +65°C, 80-98% RH.
Method 101, Condition A (90-95% RH at
5% NaCl Solution, 96 hrs).
0.1
0.01
Vibration
0.001
0.01
0.1
1
10
100-110205
AMPERE RATING
Physical
Number of Poles
Termination
1- 2 poles, + Auxiliary Switch Pole.
10-32 or M5 Screw Terminals 1/4-20 or
M6 Threaded Stud Terminals.
Standard with multi-pole constructions.
Threaded insert: #6-32 UNC-2B, or
M3X0.5-6H B ISO (2 per pole).
Handle, 1 per pole.
Moisture Resistance
Termination Barrier
Mounting
Salt Spray
Actuator
Thermal Shock
MIL-PRF-55629 and MIL-STD-202G,
Method 107G, Condition A (5-cycles at
-55°C to +25°C to +85°C to +25°C).
Internal Circuit Config. Series Trip
Materials
Housing - Glass filled Polyester
Handle - Glass filled Polyester
Line/Load Terminals - Copper Alloy.
~150 Grams (~5.3 Ounces).
Housing - Gray.
Operating Temperature -40°C to +85°C.
Weight
Standard Color
Handle - White, Black, Red, Green,
Blue, Yellow, Gray,
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
4
CX-Series Circuit Breaker - Delay Curves
Instantaneous - DC 10
Ultrashort - DC 11
Short - DC 12
Medium - DC 14
Long - DC 16
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
CX-Series Circuit Breaker UL1077 – Dimensional Specifications in. [mm]
5
2.259+0.020
[57.38+0.50]
0.265
[6.73]
0.755
[19.18]
MAXIMUM
0.502
[12.75]
0.579
[14.72]
0.380
[9.65]
1.719
[43.66]
+0.050
–0.020
+1.27
–0.50
3.094
78.59
1.843+0.020
[46.81+0.50]
2.062+0.020
[52.37+0.50]
30.0º
1.052
[26.72]
0.124
[3.16]
SHOWN WITH STUD
TERMINAL CONFIGURATION
0.626+0.020
[15.90+0.50]
2.264+0.020
[57.51+0.50]
1.017
[25.82]
2.280
[57.91]
1.515
1.520
[38.48]
[38.61]
MAXIMUM
2.259
[57.38]
0.760
[19.30]
3.672
[93.268]
0.156 TYP
[3.96]
1.062
[26.97]
2.062
[52.37]
0.750 TYP
[19.05]
CX1
CX2
CX3
0.625
[15.88]
SHOWN WITH SCREW
TERMINAL CONFIGURATION
TOLERANCES +.005[.12]
2.736
0.744
[18.90]
[69.49]
(WITH SCREW TERMINAL)
2.946
[74.83]
(WITH STUD TERMINAL)
3.276
[83.21]
(UNFOLDED BARRIER)
2.232
[56.69]
MAXIMUM
WITH OPTIONAL
RELAY TRIP POLE
6.00
[152.4]
AUX
SWITCH
RELAY
TRIP
RELAY TRIP WIRE LEADS
( I ) 600V RATING REQUIRED MINIMUM OF 2 PROTECTED POLES
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
6
CX-Series Circuit Breaker UL489 – Dimensional Specifications in.[mm]
2.259+0.020
[57.38+0.50]
0.265
[6.73]
0.502
[12.75]
0.755
0.579
[14.72]
[19.18]
MAXIMUM
1.719
[43.66]
0.380
[9.65]
1.843+0.020
[46.81+0.50]
+0.050
–0.020
+1.27
–0.50
3.094
78.59
2.062+0.020
[52.37+0.50]
30.0º
1.052
[26.72]
0.124
[3.16]
0.626+0.020
[15.90+0.50]
2.264+0.020
[57.51+0.50]
SHOWN WITH STUD
TERMINAL CONFIGURATION
1.017
[25.82]
1.515
3.672
[93.268]
[38.48]
MAXIMUM
2.259
[57.38]
2.736
SHOWN WITH SCREW
TERMINAL CONFIGURATION
[69.49]
0.744
[18.90]
(WITH SCREW TERMINAL)
2.946
1.520
[38.61]
[74.83]
(WITH STUD TERMINAL)
0.760
[19.30]
0.078 TYP
[1.98]
3.276
[83.21]
(UNFOLDED BARRIER)
REW TERMINAL)
2.946
1.520
[38.61]
[74.83]
UD TERMINAL)
3.276
[83.21]
0.760
[19.30]
0.078 TYP
[1.98]
FOLDED BARRIER)
1.062
[26.97]
TOLERANCES +.005[.12]
2.062
[52.37]
0.750 TYP
[19.05]
0.625
[15.88]
CX1
CX2
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
CX-Series Circuit Breaker UL489B – Dimensional Specifications in. [mm]
7
OPTIONAL VOLTAGE POLE
SEE NOTE 1
POLE 1
CX3
POLE 2
CX2
POLE 3
CX3 - 2 POLE SWITCH (CX2)SHOWN
WITH OPTIONAL VOLTAGE POLE
50A-100A DEVICE, 600VDC
POLE 1
OPTIONAL VOLTAGE POLE
SEE NOTE 2
POLE 2
POLE 3
SEE NOTE 3
POLE 4
POLE 5
CX5 - 4 POLE SWITCH (CX4)SHOWN
WITH OPTIONAL VOLTAGE POLE
101A-175A DEVICE, 600VDC
Notes:
1
3 pole configuration supplied with voltage coil on pole 1. Optional location pole 3.
Consult factory.
2
3
5 pole configuration supplied with voltage coil in center pole. (Pole 3)
Line & Load connections requires bus connection as shown.
2
2
Minimum cross selection .127 in (81.94 mm )
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
8
CX-Series Circuit Breaker UL489B – Ordering Scheme
C X 2 S 0 03 810 3 2 A 06 14
8
9
10
Mounting
Inserts
11
Rating
12
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color &
Legend
Series
Actuator
Poles
Circuit
Relay Trip
Frequency
& Delay
Current Rating
1 SERIES
8 TERMINAL4,5
C
3
Stud, 1/4-20
6
Stud, M6
A
B
Stud, 1/4-20, w/ 10-32 Screw Terminals on Voltage Pole
Stud, M6, w/ M5 Screw Terminals on Voltage Pole
2 ACTUATOR
Handle, one per pole
X
9 HANDLE COLOR & LEGEND
3 POLES1,2
Acuator Color
White
I-O
A
C
F
ON-OFF
Dual
Legend Color
Black
B
D
G
J
1
2
3
4
5
6
7
8
2
3
Two
4
5
Four
Five
Black
White
Three
Red
White
Green
Blue
H
K
M
P
White
L
White
4 CIRCUIT
Switch Only
Yellow
Gray
N
Q
S
Black
S
Black
Orange
R
Black
5 RELAY TRIP VOLTAGE COIL RATING1,2
0
w/o Relay Trip Voltage Coil
10 MOUNTING INSERTS
6-32 Thread
A
B
C
D
12 VDC
24 VDC
32 VDC
48 VDC
A
B
M3 Thread
11 MAX. APPLICATION RATING
06 600VDC
6 FREQUENCY & DELAY
03 DC Switch Only
12 AGENCY APPROVAL
A
Without approvals
14
UL489B Listed
7 CURRENT RATING (AMPERES)1,3
Notes:
1
2-Pole Section
650 50.00
4-Pole Section
2 Pole Unit is required for ratings between 50A - 100A.
4 Pole Unit is required for ratings between 110A - 175A.
A Relay Trip Voltage Coil Pole may be added to either the 2 or 4 Pole construction.
The addition of this extra pole dictates a change in the designation for the number of
poles in selection 3.
811
110.00
2
3
4
5
For Current Ratings between 50A - 100A select current code 810 (100A).
For Current Ratings between 101A - 175A select current code 917 (175A).
Voltage Pole must have screw terminals.
810 100.00
917
175.00
Switch Pole must have stud terminals.
On 3 Pole Unit, Voltage Pole to be located at P1 as standard.
On 5 Pole Unit, Voltage Pole to be located at P3 as standard.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
CX-Series Circuit Breaker UL489 – Ordering Scheme
9
C X 1 B 0 14 420 2 2 A 12 G
8
9
10
Mounting
Inserts
11
Rating
12
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color &
Legend
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
8 TERMINAL
2
3
Screw Terminal, 10-32
Stud, 1/4-20
5
6
Screw Terminal, M5
Stud, M6
2 ACTUATOR
Handle, one per pole
X
9 ACTUATORCOLOR & LEGEND
Acuator Color
White
I-O
A
C
F
H
K
M
P
ON-OFF
Dual
Legend Color
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
White
White
White
Black
Black
Black
3 POLES
One
Black
1
2
Two
Red
Green
Blue
Yellow
Gray
L
4 CIRCUIT
Series Trip current
N
Q
S
(
)
B
Orange
R
5 AUXILIARY/ALARM SWITCH
w/o Aux Switch
0
10 MOUNTING INSERTS
6-32 Thread
A
B
M3 Thread
6 FREQUENCY & DELAY
11
12
14
16
DC Ultra Short
DC Short
11 MAX. APPLICATION RATING
12 250VDC
131 250 / 500VDC
DC Medium
DC Long
12 AGENCY APPROVAL
A
G
Without approvals
UL 489 Listed
76 CURRENT RATING (AMPERES)
CODE AMPERES
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
Notes:
1
250/500 rating requires two pole breaker
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
10 CX-Series Circuit Breaker UL1077 – Ordering Scheme
C X 1 B 0 14 660 6 2 B 10 C
8
9
10
Mounting
Inserts
11
Rating
12
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color &
Legend
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
8 TERMINAL
2
3
Screw Terminal, 10-32
Stud, 1/4-20
5
6
Screw Terminal, M5
Stud, M6
2 ACTUATOR
X
Handle, one per pole
9 ACTUATORCOLOR & LEGEND
Acuator Color
White
I-O
A
C
F
H
K
M
P
ON-OFF
Dual
Legend Color
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
White
White
White
Black
Black
Black
3 POLES
One
Black
1
2
Two
3
Three
Red
Green
Blue
Yellow
Gray
L
4 CIRCUIT
N
Q
S
A1
B
Switch Only no coil
G1
(
)
)
(
Relay Trip voltage
)
(
Series Trip current
Orange
R
5 AUXILIARY SWITCH
w/o Aux Switch3
10 MOUNTING INSERTS
6-32 Thread w/o terminal bus
0
A
B
M3 Thread w/o terminal bus
6 FREQUENCY & DELAY
11 MAX. APPLICATION RATING
10 300VDC
114 440VDC
065
600VDC
03
10
11
12
14
16
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
12 AGENCY APPROVAL
DC Medium
A
C
Without approvals
UL 1077 Recognized
DC Long
76 CURRENT RATING (AMPERES)
Notes:
CODE AMPERES
1
2
3
4
5
6
7
Only available when tied to a protected pole. Requires special P/N. Consult factory.
Voltage trip circuit coil not rated for continuous duty - use instantaneous delay code 10.
Contacts rated for 20A @ 80VDC
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
665 65.000
670 70.000
675 75.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
911 115.000
912 125.000
440VDC rating not available with factory installed terminal bus
600VDC only available with factory installed terminal bus
Single pole units available up to 125A, multipole units limited to 100A max.
3-pole units must include one auxiliary switch pole (circuit code A or G).
Requires special P/N. Consult factory.
8
Screw terminals are limited to 50A max.
REV_CB_CX_1112
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
相关型号:
©2020 ICPDF网 联系我们和版权申明